Copper & Aluminum Wire Ampacity Charts 

(Per 2024 Canadian Electrical Code) 

The following charts reflect the acceptable Copper & Aluminum Wire Ampacities for the three most common wire insulation ratings per Tables 2 & 4 of the 2024 Canadian Electrical Code. 

These charts for Copper & Aluminum Wire Ampacity are for 3 or less conductors in a cable or raceway, with a wire insulation voltage rating under 5000v. 

For ambient temperatures over 30 degrees Celsius, or any situation in which there are more than 3 conductors inside of a cable or raceway, it is likely the allowable wire ampacities will change per correction factors described in the electrical code. If you are unsure of anything, consult a professional electrician before commencing work! 

Remember to apply CEC Rule 4-006 and de-rate your ampacity based on equipment temperature markings. Generally speaking, this is 60 deg. Celsius for all standard residential panel lugs, breakers, outlets & other components sized at less than #1awg. unless otherwise specified. (Meaning, you should you use the 60 deg. Chart unless you know otherwise.) 

Disclaimer: 

Improper use of the information below can cause injury or damage to both personnel & property! By using these charts, you agree to absolve Celtex Electric & Automation (Celtex Industries Limited) of liability for costs incurred due to their misuse, damage to or loss of property, injury or death of personnel and/or animals & all other forms of loss caused by improper application of the below information. Consult the Electrical & Building Codes in your municipality before performing any kind of electrical work. 

Copper & Aluminum Wire Ampacity Chart 

(Insulation Temperature Rating: 60c) 

Size (AWG/kcmil) Copper Max Amperage (A) Aluminum Max Amperage (A) Copper Use Case Aluminum Use Case 
14 15 N/A Lighting, Small Appliances None. Not allowed by CEC. 
12 20 15 Small Appliances, Outlets Outlets 
10 30 25 Water Heaters, AC Water Heaters 
40 35 Electric Ranges Electric Ranges 
55 40 Subpanels Subpanels 
70 55 Main Panel Feeds Main Panel Feeds 
85 65 Feeders Feeders 
95 75 Main Feeds Main Feeds 
110 85 Main Feeds Main Feeds 
1/0 125 100 Main Feeds Main Feeds 
2/0 145 115 Main Feeds Main Feeds 
3/0 165 130 Service Entrances Service Entrances 
4/0 195 150 Service Entrances Service Entrances 
250 kcmil 215 170 Large Service Feeds Large Service Feeds 
300 kcmil 240 195 Large Service Feeds Large Service Feeds 
350 kcmil 260 210 Large Service Feeds Large Service Feeds 
400 kcmil 280 225 Industrial Loads Industrial Loads 
500 kcmil 320 260 Heavy Loads Heavy Loads 
600 kcmil 350 285 Heavy Industrial Heavy Industrial 

Did you de-rate your ampacities properly? Consult the electrical code! 

CELTEX.CA

Copper & Aluminum Wire Ampacity Chart 

(Insulation Temperature Rating: 75c) 

Size (AWG/kcmil) Copper Max Amperage (A) Aluminum Max Amperage (A) Copper Use Case Aluminum Use Case 
14 20 N/A Lighting, Small Appliances None. Not allowed by CEC. 
12 25 20 Small Appliances, Outlets Outlets 
10 35 30 Water Heaters, AC Water Heaters 
50 40 Electric Ranges Electric Ranges 
65 50 Subpanels Subpanels 
85 65 Main Panel Feeds Main Panel Feeds 
100 75 Feeders Feeders 
115 90 Main Feeds Main Feeds 
130 100 Main Feeds Main Feeds 
1/0 150 120 Main Feeds Main Feeds 
2/0 175 135 Main Feeds Main Feeds 
3/0 200 155 Service Entrances Service Entrances 
4/0 230 180 Service Entrances Service Entrances 
250 kcmil 255 205 Large Service Feeds Large Service Feeds 
300 kcmil 285 230 Large Service Feeds Large Service Feeds 
350 kcmil 310 250 Large Service Feeds Large Service Feeds 
400 kcmil 335 270 Industrial Loads Industrial Loads 
500 kcmil 380 310 Heavy Loads Heavy Loads 
600 kcmil 420 340 Heavy Industrial Heavy Industrial 

Did you de-rate your ampacities properly? Consult the electrical code! 

CELTEX.CA

Copper & Aluminum Wire Ampacity Chart 

(Insulation Temperature Rating: 90c) 

Size (AWG/kcmil) Copper Max Amperage (A) Aluminum Max Amperage (A) Copper Use Case Aluminum Use Case 
14 25 N/A Lighting, Small Appliances Not acceptable for use. 
12 30 25 Small Appliances, Outlets Outlets 
10 40 35 Water Heaters, AC Water Heaters 
55 45 Electric Ranges AC, Misc. 
75 55 Subpanels Subpanels 
95 75 Panel Feeds Panel Feeds 
115 85 Feeders Feeders 
130 100 Main Feeds Main Feeds 
145 115 Main Feeds Main Feeds 
1/0 170 135 Main Feeds Main Feeds 
2/0 195 150 Main Feeds Main Feeds 
3/0 225 175 Service Entrances Service Entrances 
4/0 260 205 Service Entrances Service Entrances 
250 kcmil 290 230 Large Service Feeds Large Service Feeds 
300 kcmil 320 260 Large Service Feeds Large Service Feeds 
350 kcmil 350 280 Large Service Feeds Large Service Feeds 
400 kcmil 380 305 Industrial Loads Industrial Loads 
500 kcmil 430 350 Heavy Loads Heavy Loads 
600 kcmil 475 385 Heavy Industrial Heavy Industrial 

Did you de-rate your ampacities properly? Consult the electrical code! 